| Abstrak (Bhs. Indonesia) | Commissioning adalah serangkaian kegiatan pemeriksaan dan pengujian instalasi tenaga listrik yang telah selesai dikerjakan dan akan dioperasikan. Salah satu peralatan yang mendapatkan pemeriksaan dan pengujian adalah pengaman busbar. Dengan menggunakan prinsip Hukum Kirchoff arus, maka arus yang memasuki busbar sama dengan arus yang meninggalkan busbar. Relai differensial akan membaca perbedaan nilai arus yang masuk, sehingga ketika nilai arus tersebut melebihi kondisi-kondisi yang ditentukan maka relai akan bekerja untuk memutus PMT. Variabel-variabel yang perlu diperhatikan adalah arus kerja dan arus penahan yang masuk ke dalam relai. Commissioning tersebut disimulasikan dengan menggunakan program simulink pada MATLAB dengan menggambarkan dua diameter yang akan diuji dengan dua jenis pengujian. Dengan mengatur relai differensial dengan slope 0,8, dan arus differensial minimal 0,2 I/In. Pengujian individual dilakukan dengan memasukan dua arus yang berbeda. Pengujian stabilitas dilakukan dengan memasukkan relai differensial ke dalam sistem, dengan mengalirkan arus melalui dua diameter yang dihubung seri maka karakteristik relai terhadap perubahan polaritas akan terlihat. Dari kedua pengujian tersebut, pengaman busbar akan dikatakan layak jika nilai-nilai yang terbaca sesuai dengan prinsip kerja dan karakterisik dari relai differensial itu sendiri. |
| Abtrak (Bhs. Inggris) | Commissioning are series of checking and testing activities of power system installation had been finished and will be operated. Either one devices that gets checking and testing is busbar protection. By used Kirchoff’s Current Law, the current come into busbar, even with the current come out from busbar. Differential relay will sense difference of current value, so as it’s above that on the given condition, then relay will be disconnect circuit breaker. Commissioning are done at the moment of electrical power system is unoperated, then on the practice or simulating, using of power source is from external system. Variabels will be concerned are operate current and restraint current. Commissioning were simulated by simulink program on MATLAB R 2013a, with illustrating of 2 bays will be tested by two kinds of testing. Relay Differential’s slope was set by 0,8 , and minimal differential current was set by 0,2I/In. Individual testing did with injected two difference of current values. Stabilitate testing did with injected current on the system, with injection current pass through two bays series connected then characteristic of relay about polarity changing will be observed. From both tests, the busbar protection will be passed if the values are accord with principle of operate and relay differential’s characteristic itself. |
| Kata kunci | Commissioning, Busbar, Relai, Differensial, Penahan, Slope, Simulink |
| Pembimbing 1 | Hari Prasetijo |
| Pembimbing 2 | Daru Tri Nugroho |
| Pembimbing 3 | - |
| Tahun | 2014 |
| Jumlah Halaman | 7 |
| Tgl. Entri | 2014-07-21 11:19:11.331363 |