Judul ArtikelANALISIS PENGARUH PEMBEBANAN TERHADAP EFISIENSI TRANSFORMATOR
UNIT 1&2 DI PLTA TULIS
Abstrak (Bhs. Indonesia)Pembangkit Listrik Tenaga Air (PLTA) merupakan sumber energi terbarukan yang berperan
penting dalam sistem ketenagalistrikan nasional. Transformator dalam PLTA berfungsi menaikkan tegangan
output generator, namun efisiensinya sangat dipengaruhi oleh kondisi pembebanan. Beban yang tidak optimal
dapat menimbulkan rugi daya seperti rugi tembaga dan rugi inti, sehingga menurunkan efisiensi sistem.
Penelitian ini menganalisis pengaruh pembebanan terhadap efisiensi transformator Unit 1 dan Unit 2 di
PLTA Tulis, berdasarkan data logsheet Desember 2024. Perhitungan mencakup daya semu, rugi-rugi, dan
efisiensi transformator. Hasil menunjukkan efisiensi meningkat seiring bertambahnya beban hingga titik
optimal, lalu menurun. Efisiensi teoritis maksimum Unit 1 sebesar 99,44% pada beban 52,03%, dan Unit 2
sebesar 99,43% pada beban 35–45%. Efisiensi aktual Unit 1 berkisar antara 95,00%–95,72%, sedangkan Unit 2 antara 92,67%–95,69%. Selisih antara nilai ideal dan aktual menunjukkan pentingnya pengelolaan beban yang optimal untuk menjaga kinerja sistem transformator di lapangan.
Abtrak (Bhs. Inggris) Hydroelectric Power Plant (PLTA) is a renewable energy source that plays an important role in
the national electricity system. The transformer in a PLTA functions to increase the generator output voltage,
but its efficiency is greatly influenced by loading conditions. Suboptimal loads can cause power losses such
as copper losses and core losses, thereby reducing system efficiency. This study analyzes the effect of loading
on the efficiency of transformers Unit 1 and Unit 2 at the Tulis PLTA, based on logsheet data from December
2024. The calculation includes apparent power, losses, and transformer efficiency. The results show that
efficiency increases with increasing load to the optimal point, then decreases. The maximum theoretical
efficiency of Unit 1 is 99.44% at a load of 52.03%, and Unit 2 is 99.43% at a load of 35–45%. The actual
efficiency of Unit 1 ranges from 95.00%–95.72%, while Unit 2 is between 92.67%–95.69%. The difference
between ideal and actual values shows the importance of optimal load management to maintain the
performance of transformer systems in the field.