Judul ArtikelANALISIS KONSUMSI ENERGI LISTRIK PADA SISTEM PENDINGIN/AIR CONDITIONER DI
GEDUNG PT PERTAMINA PATRA NIAGA FUEL TERMINAL REWULU
Abstrak (Bhs. Indonesia)Analisis konsumsi energi pada Gedung PT Pertamina Patra Niaga Fuel Terminal Rewulu bertujuan untuk
menganalisis konsumsi energi yang berfokus pada sistem pendingin atau air conditioner pada Gedung PT Pertamina Patra Niaga Fuel Terminal Rewulu. Penelitian ini berfokus pada audit energi awal (preliminary audit) dengan pengumpulan data langsung dari lapangan, hanya pada gedung yang difungsikan untuk bekerja. Hasil analisis menunjukkan bahwa sistem pendingin di Gedung PT Pertamina Patra Niaga Fuel Terminal Rewulu secara keseluruhan tergolong efisien. Nilai kinerja sistem pendingin dengan CSPF menunjukkan kinerja sangat baik, namun beberapa area seperti aula membutuhkan perbaikan untuk meningkatkan efisiensi. Suhu ruangan umumnya sesuai standar SNI, tetapi beberapa ruangan seperti
Control Room dan Ruang Server memiliki suhu terlalu rendah bernilai 21°C, yang dapat meningkatkan konsumsi energi. Rekomendasi Peluang Hemat Energi (PHE) meliputi penyesuaian suhu, jam operasional, penggunaan AC aktif di setiap ruangan dan penyesuaian kapasitas AC sesuai kebutuhan ruangan. Penerapan PHE 1 dan PHE 2 berhasil menghemat energi hingga 15,87% dan 15,38%, dengan penghematan biaya masing-masing Rp 2.591.531,92 dan Rp 1.160.487,91 per bulan.
Abtrak (Bhs. Inggris)The analysis of energy consumption at the PT Pertamina Patra Niaga Fuel Terminal Rewulu building aims
to evaluate energy usage, focusing on the cooling system or air conditioning in the building. This study emphasizes a preliminary energy audit through direct on-site data collection, specifically targeting buildings designated for work activities. The analysis results indicate that the cooling system at PT Pertamina Patra Niaga Fuel Terminal Rewulu Building is generally efficient. The cooling system's performance, as indicated by the CSPF value, is classified as excellent. However, certain areas, such as the auditorium, need improvement to enhance efficiency. Room temperatures generally comply with the SNI standards, but some spaces, such as the Control Room and Server Room, have excessively low temperatures of 21°C, which may increase energy consumption. The recommended Energy Saving Opportunities (PHE) include temperature adjustments, operational hours optimization, the use of active air conditioners in each room, capacity adjustments based on room needs. The application of PHE 1 and PHE 2 successfully reduced energy consumption by 15.87% and 15.38%, respectively, resulting in cost savings of Rp 2,591,531.92 and Rp 1,160,487.91 per month.
Kata kunciEfisiensi Energi, Sistem Pendingin (AC), Cooling Seasonal Performance Factor (CSPF)