Judul ArtikelANALISIS HASIL PENGUJIAN KELAYAKAN OPERASI PEMUTUS TENAGA BAY 7AB3
GARDU INDUK 500 KV KESUGIHAN AKIBAT KEBOCORAN GAS SF6
PT.PLN (Persero) ULTG PURWOKERTO
Abstrak (Bhs. Indonesia) Gardu induk berperan penting dalam sistem transmisi listrik, dengan Pemutus Tenaga (PMT) yang
melindungi peralatan dari gangguan listrik, seperti hubungan singkat, dengan memutus aliran listrik secara otomatis.
Pemeliharaan rutin PMT, yang meliputi pengujian tahanan isolasi, tahanan kontak, keserempakan kontak, dan kemurnian
gas SF6, sangat penting untuk menjaga keandalannya. Penelitian ini mengevaluasi pengaruh pemeliharaan terhadap
keandalan PMT di bay 7AB3 dan 7AB5 pada gardu induk 500 kV Kesugihan, dengan membandingkan data pemeliharaan
dengan standar PLN. Hasil penelitian menunjukkan bahwa tahanan isolasi dan arus bocor PMT masih memenuhi standar,
meskipun rugi daya akibat tahanan kontak terus meningkat seiring waktu. Pengujian keserempakan kontak juga memenuhi
standar, namun kemurnian gas SF6 mengalami fluktuasi, dengan penurunan tekanan gas pada tahun 2023 yang
mengindikasikan kebocoran gas SF6. Meski begitu, pengukuran kemurnian gas berdasarkan dew point dan kandungan
SO2 masih memenuhi syarat minimum yang ditetapkan.
Abtrak (Bhs. Inggris)Substations play an important role in the electricity transmission system, with Power Breakers (PMTs)
protecting equipment from electrical faults, such as short circuits, by automatically cutting off the flow of electricity.
Routine maintenance of PMTs, which includes testing insulation resistance, contact resistance, contact tightness, and SF6
gas purity, is essential to maintain their reliability. This study evaluates the effect of maintenance on PMT reliability in
bays 7AB3 and 7AB5 of the 500 kV Kesugihan substation, by comparing maintenance data with PLN standards. The
results show that the insulation resistance and leakage current of PMTs still meet the standards, although the power loss
due to contact resistance continues to increase over time. Tests of contact tightness also met the standard, but SF6 gas
purity fluctuated, with a drop in gas pressure in 2023 indicating SF6 gas leakage. However, gas purity measurements
based on dew point and SO2 content still meet the minimum requirements.
Kata kunciPemutus Tenaga (PMT), Tahanan Isolasi, Tahanan Kontak, Keserempakan Kontak dan Kemurnian Gas SF6