Judul ArtikelANALISIS PERBANDINGAN KINERJA RELAY JARAK PROTEKSI SALURAN TRANSMISI 150 KV BAY BUMIAYU
Abstrak (Bhs. Indonesia)Untuk melindungi saluran transmisi antara Gardu Induk Kalibakal dan Gardu Induk Bumiayu, sistem proteksi utama yang digunakan adalah relay jarak. Fungsinya adalah untuk mengamankan saluran transmisi dengan mendeteksi dan merespons gangguan seperti hubung singkat. Distance relay bekerja dengan membandingkan besaran impedansi gangguan pada saluran dengan impedansi setting serta membagi daerah proteksi menjadi beberapa cakupan yaitu zone 1, zone 2 dan zone 3. Penelitian ini dilakukan untuk menganalisis setting distance relay yang terdapat pada saluran transmisi GI Kalibakal-GI Bumiayu dengan menggunakan perhitungan manual yang sesuai dengan standar standar Institute of Electrical and Electronics Engineers (IEEE) dan Standar PLN. Pada penelitian ini juga dilakukan analisis hubung singkat gangguan hubung singkat pada fasa yang tersedia ke tanah dari arah GI Kalibakal ke GI Bumiayu di beberapa titik gangguan yang dinyatakan dalam satuan persen (%) pada penghantar menggunakan ETAP. Didapatkan hasil perhitungan setting relay jarak pada zona 1 sebesar 6,277 Ω, pada zona 2 sebesar 9,77 Ω, dan pada zona 3 sebesar 15,966 Ω. Perbandingan antara hasil perhitungan manual dan data aktual di lapangan tidak terlalu berbeda jauh sehingga dapat disimpulkan bahwa setting dan waktu kerja relay jarak yang digunakan sudah sesuai dengan standar yang digunakan yaitu standar IEEE std C37.113.2015 dan SPLN 52-1 :1984
Abtrak (Bhs. Inggris)To protect the transmission line between the Kalibakal Main Substation and the Bumiayu Main Substation, the primary protection system used is distance relay. Its function is to secure the transmission line by detecting and responding to disturbances such as short circuits. The distance relay operates by comparing the impedance of the disturbance on the line with the set impedance and dividing the protection zone into several coverage areas: zone 1, zone 2, and zone 3. This study was conducted to analyze the settings of the distance relay on the Kalibakal-Bumiayu transmission line using manual calculations in accordance with the Institute of Electrical and Electronics Engineers (IEEE) and PLN standards. The study also analyzed short circuit faults from the Kalibakal Substation to the Bumiayu Substation at various points, expressed in percentage (%) on the conductor, using ETAP. The calculation results obtained relay settings for zone 1 is 6.277 Ω, for zone 2 is 9.77 Ω, and for zone 3 is 15.966 Ω. The comparison between the manual calculation results and actual field data is not significantly different, concluding that the settings and operation timing of the distance relay used are in accordance with the standards, namely IEEE std C37.113.2015 and SPLN 52-1:1984..
Kata kunciSaluran transmisi, relay distance, gangguan hubung singkat
Pembimbing 1Ir. Daru Tri Nugroho S.T. M.T.
Pembimbing 2Dr. Mulki Indana Zulfa, S.T.,M.T.
Pembimbing 3
Tahun2023
Jumlah Halaman10
Tgl. Entri2023-08-31 00:47:32.982526
Cetak Bukti Unggah
© Universitas Jenderal Soedirman 2026 All rights reserved.