Judul ArtikelANALISIS ALIRAN DAYA LISTIK PADA SISTEM BOP (BALANCE OF PLANT) DI PLTU TANJUNG JATI B UNIT 5 & 6 KAPASITAS
2 X 1000 MW
Abstrak (Bhs. Indonesia)Analisis Aliran Daya Listrik adalah suatu studi untuk merencanakan dan mengetahui besarnya daya dalam suatu sistem tenaga listrik serta untuk mengetahui besar rugi daya (Losses) dan jatuh tegangan yang ada apakah masih memenuhi batas-batas yang telah ditentukan. Analisis aliran daya ini dilakukan pada sistem BOP di PLTU Tanjung Jati B unit 5 dan 6. PLTU (Pembangkit Listrik Tenaga Uap) memiliki komponen pembantu atau bisa disebut sistem BOP (Balance of Plant). Untuk menjaga kondisi sistem BOP agar tetap bisa bekerja secara efektif, dilakukan analisis aliran daya. Dari hasil simulasi dengan ETAP (Electrical Transient Analyzer Program) versi 12.6, pada awalnya terdapat bus yang mengalami kondisi overvoltage, kemudian setelah dilakukan pengaturan pada Tap Transformator pada sisi primer, kondisi semua bus mengalami perbaikan terutama bus yang mengalami kondisi overvoltage menjadi normal. Pada simulasi kedua setelah kondisi keseluruhan sistem normal, diketahui bahwa sistem BOP memiliki drop voltage terendah pada bagian Coal Handling yaitu sebesar -0,0535 kV atau sebesar -1,784%, dan memiliki drop voltage tertinggi pada bagian Coal Yard yaitu sebesar 0,1277 kV atau 1,277 %. Disisi lain, nilai losses pada simulasi kedua mengalami kenaikan dari 636,9 kW (sebelum pengaturan Tap Transformator) menjadi 645,3 kW sehingga mengalami kenaikan yang terpaut kecil yaitu sebesar 8,4 kW dari total keseluruhan losses.
Abtrak (Bhs. Inggris)Electric Power Flow Analysis is a study to plan and determine the amount of power in an electric power system and to determine the amount of power loss (Losses) and the voltage drop that is there whether it still meets predetermined limits. This power flow analysis is carried out on the BOP system in Tanjung Jati B PLTU units 5 and 6. The PLTU (Steam Power Plant) has an auxiliary component or can be called a BOP (Balance of Plant) system. To maintain the condition of the BOP system so that it can still work effectively, a power flow analysis is carried out. From the simulation results with version 12.6 of ETAP (Electrical Transient Analyzer Program), at first there were buses that experienced overvoltage conditions, then after adjusting the Tap Transformator on the primary side, the condition of all buses had improved, especially buses that experienced overvoltage conditions became normal. In the second simulation after the overall condition of the system is normal, it is known that the BOP system has the lowest drop voltage in the Coal Handling section which is -0.0535 kV or -1.778%, and has the highest drop voltage in the Coal Yard section of 0.1277 kV or 1,277%. On the other hand, the value of losses in the second simulation has increased from 636.9 kW (before setting the Tap Transformator) to 645.3 kW so that it has a small increase in value of 8.4 kW from the total overall losses.
Kata kunciAnalisis Aliran Daya, Sistem BOP, Rugi Daya, ETAP.
Pembimbing 1Winasis, S.T., M.Eng.
Pembimbing 2Arief Wisnu W, B.Eng(Hons)., M.Eng.
Pembimbing 3
Tahun2019
Jumlah Halaman13
Tgl. Entri2019-05-05 15:31:59.201275
Cetak Bukti Unggah
© Universitas Jenderal Soedirman 2026 All rights reserved.