| Judul Artikel | ANALISIS KOORDINASI PENGAMAN OVERCURRENT RELAY, GROUND FAULT RELAY, RECLOSER, DAN FUSE CUT OUT TERHADAP GANGGUAN ARUS HUBUNG SINGKAT PADA PENYULANG KALIBAKAL-09 PT. PLN(PERSERO) RAYON PURWOKERTO AREA PURWOKERTO. |
| Abstrak (Bhs. Indonesia) | Pada penyulang 20 kV terdapat peralatan proteksi arus lebih antara lain yaitu Over Current Relay (OCR), Ground Fault Relay (GFR), Recloser, dan Fuse Cut Out (FCO). Peralatan proteksi yang dipasang di penyulang 20 kV harus dapat berkoordinasi dengan baik antara satu dengan lainnya. Studi ini dilakukan untuk menganalisis koordinasi dari peralatan pengaman pada penyulang Kalibakal-09 antara lain dengan menganalisis gangguan hubung singkat, menentukan nilai setting peralatan pengaman, dan mengetahui waktu kerja relay terhadap titik gangguan serta melihat koordinasi antar relay tersebut dan membandingkan hasil perhitungan terhadap realisasi dilapangan. Metode yang digunakan dalam analisis koordinasi dari peralatan pengaman yaitu perhitungan impedansi total di bus 20 kV, menghitung arus hubung singkat baik manual maupun menggunakan simulasi pada software ETAP 12.6.0 yang terjadi di bus sisi 20 kV, baik untuk arus hubung singkat 3 𝚽, 2𝚽 maupun 1𝚽, menentukan setting relai arus lebih (OCR) dan ground fault relay (GFR) di sisi feeder 20 kV, menentukan setting recloser dan fuse cut out di feeder, dan menganalisis setting yang sudah dihitung, yaitu membandingkan nilai perhitungan dengan keadaan sistem proteksi yang sebenarnya. Berdasarkan hasil analisis dan perhitungan waktu kerja dari peralatan pengaman, ketika terjadi gangguan arus hubung singkat pada daerah percabangan, maka FCO akan melakukan pemutusan lebih dulu, karena untuk mengantisipasi menghindari pemadaman yang lebih luas, sehingga dapat disimpulkan bahwa secara keseluruhan setting OCR, GFR, Recloser, dan FCO yang ada dilapangan atau pada titik gangguan masih dalam kondisi baik. |
| Abtrak (Bhs. Inggris) | At 20 kV feeders are overcurrent protection equipment, among others, Over Current Relay (OCR), Ground Fault Relay (GFR), Recloser, and Fuse Cut Out (FCO). Protection equipment installed in 20 kV feeders must be able to coordinate well with each other. This study was conducted to analyze the coordination of safety equipment on the feeder Kalibakal-09, among others, by analyzing the short circuit, determine the value of setting safety equipment, and know when the relay to the point of interference and see coordination between the relay and compare the results of the calculation of the actual field. The method used in the analysis of the coordination of the safety equipment that is the calculation of the total impedance on the bus 20 kV, calculate short circuit current either manually or using simulation on ETAP software 12.6.0 that occurred on the bus side of 20 kV, both for the short circuit current 3 Φ, 2Φ and 1Φ, specify the setting relay overcurrent (OCR) and ground fault relay (GFR) on the side of the feeder 20 kV, specify the settings Recloser and fuse cut-out in the feeder, and analyze the settings that have been calculated, comparing the values calculated with the state of the protection system in fact. Based on the analysis and calculation of working time of protective equipment, when an interruption occurs the short circuit current in the area of branching, the FCO will terminate first, as to anticipate avoid blackouts wider, so that it can be concluded that the overall setting of the OCR, GFR, Recloser and FCO that exist in the field or at the point of interruption is still in good condition. |
| Kata kunci | Peralatan Proteksi Penyulang, Koordinasi Sistem Pengaman, Simulasi ETAP |
| Pembimbing 1 | Hari Prasetijo, ST., MT |
| Pembimbing 2 | Eko Murdyantoro, ST., MT |
| Pembimbing 3 | |
| Tahun | 2017 |
| Jumlah Halaman | 98 |
| Tgl. Entri | 2017-04-19 22:25:20.181753 |
|---|