| Judul Artikel | ANALISA PENGGUNAAN STATIC VAR COMPENSATOR (SVC) UNTUK MEMPERBAIKI PROFIL TEGANGAN PADA FEEDER LOMANIS 01 (LMS01) JARINGAN DISTRIBUSI TEGANGAN MENENGAH 20 kV PT. PLN (PERSERO) APJ CILACAP |
| Abstrak (Bhs. Indonesia) | Sistem distribusi merupakan bagian dari sistem tenaga listrik yang berguna untuk menyalurkan tenaga listrik dari sumber daya listrik besar sampai ke konsumen. Dalam proses penyalurannya dari pembangkit sampai ke pelanggan akan timbul rugi-rugi daya, tegangan jatuh, dan rugi energi. Pada penelitian ini akan dilakukan perbaikan untuk memperbaiki profil tegangan yaitu berupa drop tegangan dan losses di jaringan distribusi 20kV pada feeder Lomanis 01 (LMS01). Analisis yang dilakukan berupa simulasi menggunakan software ETAP Power Station 7.5.0 dengan menambahkan Static VAR Compensator (SVC) pada bus feeder yang terjadi losses dan drop tegangan yang besar guna proses perbaikan profi tegangan tersebut agar sesuai dengan standar yang diizinkan yaitu SPLN 1: 1995 yaitu maksimum +5% dan minimum -10%. Dari analisis yang dilakukan, didapatkan nilai drop tegangan sebesar 18.498 kV dengan penurunan sebesar 7.51% dari tegangan keluaran trafo sebesar 20 kV. Setelah dilakukan simulasi, penempatan SVC yang optimal berada pada bus 4 hal tersebut didapatkan dari perhitungan rata-rata nilai drop tegangan terkecil. Dengan pemasangan SVC sebesar 43.49 MVar pada bus 4 mampu menguragi drop tegangan dan meningkatkan profil tegangan pada ujung feeder yang awalnya sebesar 18.498 kV menjadi 19.561 kV. |
| Abtrak (Bhs. Inggris) | The distribution system is a part of electricity power system that is useful to deliver electricity power from large power electricity resources to the consumer. In the delivery process from electricity plant to customers, will raised loss power, drop voltages, and loss energy. This research will be carried lot of repairs to improve the voltage profile such as drop voltages and losses in the distribution network at 20kV feeder Lomanis 01 (LMS01). Analysis used simulation program and using software ETAP Power Station 7.5.0. By adding Static VAR Compensator (SVC) on the feeder bus that have some problem of huge losses and drop voltages in order to repairing the voltage profit process itself. Then, it will be match with the permitted standards of SPLN 1: 1995 which is, the maximum +5% and minimum -10%. From the analysis, score level point show at 18.498 kV drop voltages with the decreasing score level point at 7:51% from the transformer output voltage at 20 kV. In his analysis those condition is still in critical voltage condition. In those conditions, repairing is needed in order to get results in marginal voltage conditions. After the simulation, optimal apply of SVC is on bus 4. It’s obtained by calculating from the average value of smallest drop voltages. With the installation of SVC at 43.49 MVAR on bus 4 is able to reduce the drop voltages and raise the profile of the voltage itself in the end of the feeder which originally amounted from 18.498 kV become 19.561 kV. |
| Kata kunci | critical voltage, drop tegangan, losses, marginal voltage, SVC |
| Pembimbing 1 | Daru Tri Nugroho S.T., M.T., |
| Pembimbing 2 | Dr. Eng. Suroso S.T., M.Eng., |
| Pembimbing 3 | |
| Tahun | 2015 |
| Jumlah Halaman | 8 |
| Tgl. Entri | 2015-08-18 16:08:34.765438 |